AGROWtEK Temperature Humidity Controller Instruction Manual

AGROWtEK Temperature Humidity Controller - Featured Image

AGROWtEK logoJARRAIBIDE ESKULIBURUA
THC
Tenperatura Hezetasun Kontrolatzailea
Argibide eskuliburua
AGROWtEK Temperature Humidity Controller

Zehaztapenak

Primary Power, RJ-45 Jack 24Vdc
Backup Power, R/C terminals 24Vac
Gehienezko Kable Distantzia 100 oin
Tenperatura tartea -20 – 60°C
Tenperaturaren zehaztasuna ¹1°C tipikoa
¹1.8°C maximum
Hezetasun-barrutia 0 – 100% RH (non-condensing) 80% RH Max Operating
Hezetasunaren zehaztasuna Âą2% 0-80% typical
Âą% 4 gehienez
Irteerako kanalak 6 Relays (G,Y1,Y2,W1,W2,HUM)
Kontaktuen balorazioa 24Vac/Vdc 1A
Berokuntza Stages 2
Hozte Stages 2
Hezetasuna Stages 1/2
Reheat Support Standard or Electric
Onartutako protokoloak GrowNET™

GUNDU JARRAIBIDE HAUEK
Produktu hau erabilera komertzialerako soilik da.

02/26 REV

©Agrowtek Inc. | www.agrowtek.com | Hazten lagunduko dizun teknologia™

Ezaugarriak

THC series Temperature and Humidity Controllers are designed for intelligent control of standard dry-contact operated HVAC systems plus dehumidifiers in growing environments. Featuring advanced reheat and external humidity control options that are unique to indoor agriculture. Operate heating, cooling, reversing valves, reheat dehumidification, and standard humidity equipment using 24VAC control.

Integration with GrowControl GCX Systems
Connects to GrowControl™ GCX Cultivation Control Systems for operation from a central controller.

  • Monitor, log, and graph the THC’s temperature and humidity data.
  • Operate from an external canopy sensor instead of the internal sensor.
  • Schedule changes to the set points.

Backup Power and Stand-Alone Operation
The THC controller can operate off of the HVAC system’s 24VAC power source to continue operating in the event that the main control system becomes disconnected or loses power. The integrated temperature/humidity sensor, on-board clock, and internally stored set points allow the unit to seamlessly continue operating and controlling the environment.

AGROWtEK Temperature Humidity Controller - Features

Simple Operation, Powerful Control
LCD display shows local temperature and humidity, output status, time/date, and more. Settings are configured quickly and easily via the button-driven menus or from the master GrowControl™ GCX controller.
Easy installation with a reversible mounting plate for junction box installation or flush wall mounting and bottom cable entry where a junction box is not available. Standard terminal block wiring connections.

GCX System Integration

The THC can operate stand-alone like a traditional thermostat, or it can be integrated with a GrowControl™ GCX facility control system.

AGROWtEK Temperature Humidity Controller - GCX System Integration

Central Monitoring
When connected to a GCX, the THC controller will report back the current sensor readings and status of each contact for data logging and real-time monitoring in the room dashboard.
Contacts can also be manually forced on or off for maintenance from the GCX interface.

AGROWtEK Temperature Humidity Controller - Central Monitoring

Scheduled Set Point Changes
The GCX controller can send updated set points and sun-rise/sun-set times on any schedule to automate changes in the room environment set points. Easily manage the set points for each room or zone from the GCX system.

AGROWtEK Temperature Humidity Controller - Scheduled Set Point Changes

Control from Canopy Sensors
Send sensor data to the THC from canopy sensors in the room for a more accurate control of the environment. If the canopy sensors become unavailable or the connection to the GCX is lost, the THC reverts to the internal sensor for control.

AGROWtEK Temperature Humidity Controller - Control from Canopy Sensors

Abisuak eta oharrak

abisua INSTALATU EDO ERABILI AURRETIK IRAKURRI ETA ULERTU ESKULIBURUA OSOA.
Failure to read, understand, and comply with warnings and installation requirements may result in property damage, personal injury, or death.

abisua KONTUZ
Do not use a power supply other than the intended or included power supply. Do not exceed the maximum ratings on the product serial label or specifications listed in this manual. Any power supply with energy levels exceeding the specifications must be current-limited or fused to prevent overcurrent to the device.

abisua KONTUZ
Do not drill or cut into the enclosure. Damage to the product from metallic debris or the tool may result.

abisua BARNEKO KOKALEKUAK BAKARRIK
Produktu hau barrualdean muntatzeko soilik diseinatuta dago eta eguraldi txarretik eta eguzki-argitik babestu behar da.

abisua OHARRA
GrowNET™ ports use standard RJ-45 connections but are NOT compatible with the Ethernet network equipment.
Do not connect GrowNET™ ports to Ethernet ports or network switch gear, or equipment damage may result.

abisua GAINTZA DIELEKTRIKOA
Koipe dielektrikoa gomendatzen da RJ-45 GrowNET™ konexioetan ingurune hezeetan erabiltzen denean.
Place a small amount of grease onto the RJ-45 plug contacts before inserting them into the GrowNET™ port.

  • Loctite LB 8423
  • Dupont Molykote 4/5
  • CRC 05105 Koipe di-elektrikoa
  • Super Lube 91016 silikonazko koipe dielektrikoa
  • Other Silicone or lithium-based insulating grease

abisua OHARRA
Do not spray the sensor with water or chemicals. Protect the sensor from direct water exposure. Always cover sensor openings when spraying chemicals or fogging.

AGROWtEK Temperature Humidity Controller - Warnings & Notices

abisua OHARRA
Do not locate the sensor near HVAC vents, humidifiers, or dehumidifiers, lighting equipment, etc. This will cause the sensor to overreact and short-cycle HVAC equipment.

abisua KONTUZ
Produktu honek Kaliforniako estatuak minbizia eta jaiotzako akatsak edo ugalketa beste kalteak sor ditzakeen produktu kimikoak izan ditzake.

Instalazio-argibideak

Kokapen-baldintzak:

  • Location must be accessible; ensure the unit will not be blocked by other equipment or fixtures.
  • The sensor must be located in sufficient air flow for accuracy; do not locate it in corners or obstructions.
  • Mount away from influences such as ventilation ducts, doorways, windows, lights, or hot equipment.
  • Mount in a dry location away from mists, sprays, drips, condensation, and rain.
  • Mount at the operator level, approximately 52-60in. from the floor.

Horma-plaka muntatu

The wall plate has a reversible design for mounting to a standard junction box or to any flat wall surface with cable entry via the bottom of the enclosure.
To install the wall plate for use with bottom cable entry, ensure the two half-circle cut-outs are facing the down position. Otherwise, install the wall plate with the cut-outs in the up position to block the openings.

AGROWtEK Temperature Humidity Controller - Mount the Wall Plate

abisua OHARRA
Do not over-tighten the cover screws or junction box screws to avoid bending the aluminum enclosure.

Prepare Connections

Connections consist of low-voltage control signals for HVAC and dehumidifiers, and an RJ-45 cable for connection to a GrowControl™ GCX Cultivation Control System.

GrowNET™ Connection (RJ-45/CAT5)
Connection to a master controller is optional, but it provides advanced control features described in the features section. Connection is made with a standard RJ-45 type connection and CAT5 or better cable. Standard Ethernet cables can be purchased from retailers if you prefer not to crimp custom cables.

HVAC System Connections (4, 5, 6, or 7-Wire)
HVAC connections include 24VAC (R), Common (C), and additional signals. The HVAC system provides backup power to the unit in the event that the GrowNET™ cable is not connected. See the example connections in the example wiring diagrams to determine thermostat cable wiring requirements.

Humidity Output Connection (2-Wire)
The humidity output is a single dry-contact that can be programmed to operate a humidifier or a dehumidifier. See connection examples in the example wiring diagrams; use two-conductor thermostat cable.

AGROWtEK Temperature Humidity Controller - Humidity Output Connection

Kableen bideratzea
Volumen baxuatage and GrowNET™ cables can be routed through conduit using a standard junction box mounting or through the bottom openings if no junction box is used (see wall plate mounting instructions.)

abisua OHARRA
Ensure cables are routed on the terminal block side of the enclosure and do not damage or short into any components on the PCB.

HVAC kableatuak

Standard HVAC systems provide 24VAC power from the system’s transformer, which acts as a backup power source when connected to a GCX system, or as a primary power source when used stand-alone. The 24VAC is also switched by onboard relays (contacts) to the HVAC system’s demand signals in order to operate the unit.

Conductors required according to HVAC system stages:

Sistema Mota Seinaleak Eroaleak
S bakarratage AC Only R, C, G, Y1 4
S bakarratage AC, Single Stage Beroa R, C, G, Y1, W1 5
S bikoitzatage AC, Single Stage Beroa R, C, G, Y1, Y2, W1 6
S bikoitzatage AC, Dual Stage Beroa R, C, G, Y1, Y2, W1, W2 7

Connect the HVAC system signals according to the labeling on the PCB and the diagram below.

AGROWtEK Temperature Humidity Controller - HVAC Wiring

Humidifier/Dehumidifier Wiring

The THC controller is capable of operating either a humidifier or a dehumidifier from the dry-contact output.
The humidifier or dehumidifier must be compatible with low-voltage kontrola.

Standard dehumidifiers manufactured by common brands such as Quest and Anden typically have a low- voltage external control connection for 24VAC control signals similar to an HVAC system. Units can be daisy- chained from unit to unit according to the manufacturer’s instructions.

Bilaketa Ereduak

AGROWtEK Temperature Humidity Controller - Quest Models

Anden Models

AGROWtEK Temperature Humidity Controller - Anden Models

Anden Setup Procedure for External Control

  1. Sakatu edozein botoi pantaila aktibatzeko eta ziurtatu unitatea "OFF" moduan ezarrita dagoela.
  2. Hold the “MODE” button for three (3) seconds to enter the installer setup menu.
  3. "Urrutiko" pantailan bistaratuko da.
  4. Sakatu "MODUA" botoia pantailan "Kanpoko desgaituta" agertu arte.
  5. Sakatu "Gora" edo "Behera" pantaila "External Enabled" moduan ezartzeko.
  6. Sakatu "MODEA" pantailan "Eginduta" agertu arte.
  7. Sakatu "ON" botoia; "Kanpokoa" pantailan agertu behar da.

Nola funtzionatzen duen

The THC controller can operate multi-stage heating and cooling equipment as well as humidification and dehumidification equipment. The THC must be properly configured to match the system that is connected. The THC can be configured to operate default conventional HVAC systems, heat pump systems, reheat options, and more.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
Depending on how the THC is configured in the Config Menu, certain menus or menu items may or may not be available to the user. Only the relevant menu items will be displayed.

Ezarri puntuak
Day & Night Set Points
The THC unit features internal set points for temperature and humidity with independent values for day and night. The day and night periods are configured in the Time menu; see sunrise and sunset times. These set points and times can be automatically updated based on a grow schedule when connected to a GrowControl™ GCX control system.

Set Point Off sets
Offsets determine when the heating and cooling (or humidification and dehumidification) stages begin and end relative to the set point.

Amaitzeko modua
Determines if the second stage of heating, cooling, or dehumidification ends at the set point (on target) or at the off set (staged)

Modua Deskribapena
Staged Stage 2 turns off at the stage 1 offset.
On Target Stage 2 turns off at the target set point.

AGROWtEK Temperature Humidity Controller - End Mode

HVAC Kontrola

The THC is designed to install and operate like a standard dry-contact wall thermostat and can handle various types of systems, including gas or electric forced air, boilers, and heat pumps (see Config Menu)
The THC supports up to two stagberogailua eta bi stages of cooling with fan control.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
When configured for reheat control, stage 1 edo stage 2 heating contact is used; see the reheat section.

Hezetasunaren Kontrola

The THC has a dedicated humidity control output contact, which can be configured for either humidification or de-humidification (default). The humidity contact is typically used to operate dehumidifiers in a growing space in coordination with standard HVAC equipment.
In addition to the humidity contact, the controller can also operate a reheat contact in order to dehumidify the space. See the reheat section for additional detail.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
Bi stages of dehumidification are available when reheat is enabled, and the humidity contact is configured for dehumidification.

Berotu Deshumidifikazioa

Two types of Reheat dehumidification systems are supported by the THC: standard and economy.

Standard Reheat
Uses output W2 (heat 2) to activate a reheat stage, and the output Y1 (compressor 1) to activate the compressor when dehumidification is required.
Reheat turns off If cooling or heating is demanded due to the temperature in the space.

Ekonomia Berotu
Uses output W1 (heat 1) to activate a heat stage, and the output Y1 (compressor 1) to activate the compressor when dehumidification is required. Reheat turns off if cooling or heating is demanded due to the temperature in the space.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
When two stages of dehumidification are present (humidity contact is a dehumidifier), the reheat contact is operated as stage 1, and the humidity contact is operated as stage 2 (supplemental dehumidification)

Eragiketa-jarraibideak

The main screen displays the real-time sensor readings from the internal sensors as well as other information, including output status, connection status, date, time, and more. Three buttons are located beneath the screen. Each button is labeled to describe its function: up, down, or enter/select.

AGROWtEK Temperature Humidity Controller - Operation Instructions

1. Gora botoia Use to scroll up in menus or increment values.
2. Behera botoia Use to scroll down in menus or decrement values.
3. Sartu botoia Use to enter a menu or confirm an entry.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
Pressing the up/down arrows from the home screen will toggle through the status displays.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
Pressing the Enter button from the home sensor display will open the main menu.

Sensor Display (Home)
The sensor display is the default (home) screen on power-up and when exiting menus.
The sensor display shows the current temperature and humidity reading that the unit is using to control the connected equipment.

AGROWtEK Temperature Humidity Controller - Sensor Display

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
The ‘x’ symbol will be displayed after the temperature units when the THC is connected to a GCX system and external sensor data is being sent to the THC. The ‘x’ symbol indicates the temperature and humidity on display are from the external sensor. Use the up/down arrows to access the status displays to view the internal sensor readings.

Egoera bistaratzeak
The status displays are accessed using the up or down buttons from the home sensor display. The buttons will increment through various information displays at the top of the screen. The bottom area of the screen displays the active output contacts.

AGROWtEK Temperature Humidity Controller - Status Displays

Tenperatura
Provides the current temperature value from the internal sensor.

AGROWtEK Temperature Humidity Controller - Temperature

Hezetasuna
Provides the current humidity value from the internal sensor.

AGROWtEK Temperature Humidity Controller - Humidity

Eguneko ordua
Provides the current time of day from the internal real-time clock.

AGROWtEK Temperature Humidity Controller - Time of Day

Day/Night Status
Indicates whether the controller is using the day or night set points.

AGROWtEK Temperature Humidity Controller - Night Status

Lineako egoera
Indicates whether the THC is online or offline.

AGROWtEK Temperature Humidity Controller - Online Status

Egoera Deskribapena
Sarean Communicating with the GCX main controller.
Lineaz kanpo Operating from internal settings and onboard sensors.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
The screen will return to the home display once the user has scrolled through all of the information displays.

Irteera-egoera
The bottom area of the status display screen indicates the active output contacts.
If the symbol for the contact is shown, the contact is activated (closed)

AGROWtEK Temperature Humidity Controller - Output Status

Elementua Ikurra Harremanetan jarri Deskribapena
1 Fx G Fan
2 C1 Y1 Hozte Stage 1
3 C2 Y2 Hozte Stage 2
4 H1 W1 Berokuntza Stage 1
5 H2 W2 Berokuntza Stage 2
6 DH / HU HUM Dehumidify / Humidify

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
If the ‘infinity’ symbol (AGROWtEK Temperature Humidity Controller - Symbol 2) is shown next to Fx, the Fan contact is in forced (on) mode and will not turn off until the Fan mode is returned to AUTO mode.

Editatu balioak
To edit a value in a menu:

  1. Navigate to the menu item you want to edit and press the Enter button.
  2. A carrot symbol (>) will appear before the value to indicate that the value is ready to edit.
  3. Use the up/down buttons to modify the value. (Hold the button down to change the value rapidly.)
  4. Press the Enter button to confirm the new value.
  5. The carrot symbol will disappear to indicate that editing is completed.

AGROWtEK Temperature Humidity Controller - Edit Values

Elementua Deskribapena
1 Name of the value or menu item.
2 The menu item value or mode.
3 The carrot symbol indicates editing mode.

Menu nagusia
The main menu is accessed from any home screen display by pressing the Enter button.
The first menu displayed is the Mode menu; press up/down to scroll through the menus, then press the Enter button to open the selected menu.

Modua
The mode menu sets the system mode: Auto, Heat, Cool, Off.

AGROWtEK Temperature Humidity Controller - Mode

Modua Deskribapena
Autoa Operate heating and cooling stages automatically.
Cool Operate only cooling stages (heat disabled)
Beroa Operate only heating stages (cooling disabled)
Desaktibatuta Do not operate any stages automatically.

Fan
The Fan menu sets the fan mode: Auto or On.AGROWtEK Temperature Humidity Controller - Fan

Modua Deskribapena
Autoa Operate the fan automatically with heat and cool stages.
On Operate the fan continuously.

Temp, Humid Menus
The Temp and Humid menus provide settings for set points.

AGROWtEK Temperature Humidity Controller - Temp, Humid Menus

Ordu menua
The Time menu configures the time of day and settings for sunrise and sunset.

AGROWtEK Temperature Humidity Controller - Time Menu

Konfigurazio menua
The Config menu provides configuration settings that control how the unit operates and informs the unit of what type of HVAC components are connected.

AGROWtEK Temperature Humidity Controller - Config Menu

Tenperatura menua
The temperature menu is where the day and night target set points and offsets are configured. Press Enter to open the Temp Menu and use the up/down buttons to scroll through the menu pages.

AGROWtEK Temperature Humidity Controller - Temperature Menu

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
When connected to a GCX control system, the temperature settings may be updated automatically from the controller according to the scheduled settings configured in the GCX control system.

Eguneko Ezarri-puntua
The day set point is adjusted by pressing Enter on the menu item. A carrot symbol (>) appears to indicate that the value is ready to adjust. Use the up/down arrows to adjust the value and press Enter to confirm.

AGROWtEK Temperature Humidity Controller - Day Setpoint

Gaueko Ezarri-puntua
The night set point is adjusted by pressing Enter on the menu item. A carrot symbol (>) appears to indicate that the value is ready to adjust. Use the up/down arrows to adjust the value and press Enter to confirm.

AGROWtEK Temperature Humidity Controller - Night Setpoint

HT1, HT2 Diff erential
Heat 1 and Heat 2 differential offsets tell the THC when to engage the first and second stagberokuntzaren es.AGROWtEK Temperature Humidity Controller - HT1, HT2 Diff erential

Modua Deskribapena
HT1 Heat 1 offset from set point.
HT2 Heat 2 offset from Heat 1 offset.

CL1, CL2 Diff erential
Cool 1 and Cool 2 differential offsets tell the THC when to engage the first and second staghozte es.

AGROWtEK Temperature Humidity Controller - CL1, CL2 Diff erential

Modua Deskribapena
CL1 Cool 1 offset from set point.
CL2 Cool 2 offset from Cool 1 offset.

Heat, Cool End Mode
The end mode determines whether the heating or cooling second stage continues to operate until the temperature set point is reached, or until the stage offset is satisfied.

AGROWtEK Temperature Humidity Controller - Heat, Cool End Mode

Humidity Menu
The humidity menu is where the day and night target set points and offsets are configured. Press Enter to open the Humid Menu and use the up/ down buttons to scroll through the menu pages.

AGROWtEK Temperature Humidity Controller - Humidity Menu

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
When connected to a GCX control system, the humidity settings may be updated automatically from the controller according to the scheduled settings configured in the GCX control system.

Eguneko Ezarri-puntua
The day set point is adjusted by pressing Enter on the menu item. A carrot symbol (>) appears to indicate that the value is ready to adjust. Use the up/down arrows to adjust the value and press Enter to confirm.

AGROWtEK Temperature Humidity Controller - Day Setpoint 2

Gaueko Ezarri-puntua
The night set point is adjusted by pressing Enter on the menu item. A carrot symbol (>) appears to indicate that the value is ready to adjust. Use the up/down arrows to adjust the value and press Enter to confirm.

AGROWtEK Temperature Humidity Controller - Night Setpoint 2

DH1, DH2 Differential
Dehumidify 1 and Dehumidify 2 differential offsets tell the THC when to engage the first and second stages of dehumidification.

AGROWtEK Temperature Humidity Controller - DH1, DH2 Diff erential

Modua Deskribapena
DH1 Dehumidify 1 off set from set point.
DH2 Dehumidify 2 off set from Heat 1 Dehumidify.*

*If two stages of dehumidification are available (external dehumidification and reheat)

Dehumidify End Mode
The end mode determines whether the second stage of dehumidification continues to operate until the humidity set point is reached or until the stage off set is satisfied.

AGROWtEK Temperature Humidity Controller - Dehumidify End Mode

Modua Deskribapena
On Targ Stage 2 will turn off at the set point.
Staged Stage 2 will turn off at the offset (where stage 1 started)

Ordu menua
The time menu is where the sunrise and sunset times are configured, and where the real-time clock’s current time and date are set. Press Enter to open the Time Menu and use the up/down buttons to scroll through the menu pages.

AGROWtEK Temperature Humidity Controller - Time Menu 2

Egunsentia
The Sunrise time tells the THC when to begin the day mode and use the day set points for control.

AGROWtEK Temperature Humidity Controller - Sunrise

Ilunabarra
The Sunset time tells the THC when to begin the night mode and use the night set points for control.

AGROWtEK Temperature Humidity Controller - Sunset

Denbora
This menu allows the user to manually set the real-time clock’s time.

AGROWtEK Temperature Humidity Controller - Time

Data
This menu allows the user to manually set the real-time clock’s date.

AGROWtEK Temperature Humidity Controller - Date

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
When connected to a GCX control system, the current time and date will be synchronized automatically, and the sunrise and sunset times may be updated according to schedules as set on the GCX.

Adjusting Time Menu Values

  1. Press the Enter button when the desired time menu page is displayed; this will begin the editing mode.
  2. A cursor will appear below the first field.
  3. Use the Up/Down buttons to adjust the value.
  4. Press the Enter button to confirm the value and move the cursor to the next field.
  5. Continue editing fields until the last field is complete and the cursor is no longer visible.

AGROWtEK Temperature Humidity Controller - Adjusting Time Menu Values 1

Zenbakia Deskribapena
1 Hours (24-hour format)
2 Minutuak
3 Segundoak
4 Kurtsorea

AGROWtEK Temperature Humidity Controller - Adjusting Time Menu Values 2

Zenbakia Deskribapena
1 Urtea
2 Hilabetea
3 Eguna
4 Kurtsorea

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
Holding down the buttons when editing a value will change it more rapidly.

Konfigurazio menua
The time menu contains settings that configure the THC to operate in different ways and according to the type of equipment that is connected to the contacts.

AGROWtEK Temperature Humidity Controller - Config Menu 2

Sistema mota
The THC can operate multiple types of HVAC systems:

AGROWtEK Temperature Humidity Controller - System Type

Mota Deskribapena
Standrd Standard HVAC system (forced air, boiler)
HT Pump Heat pump-based system.

Berotze modua
Reheat can be enabled for dehumidification purposes if installed.

AGROWtEK Temperature Humidity Controller - Reheat Mode

Modua Deskribapena
Desaktibatuta Reheat modes are not enabled.
Standrd Standard, Uses Heat 2 (W2) contact for reheat.
Electrc Electric, Uses Heat 1 (W1) contact for reheat.

Dehumidification Stage 1
When two dehumidification stages are available, this menu allows selection of which stage will be the primary stage (stage 1)

Ezarpena Deskribapena
Berotu Use reheat as the primary dehumidification stage.
Externl Use the humidity contact as the primary dehumidification stage.

AGROWtEK Temperature Humidity Controller - Dehumidifi cation Stage 1

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
This menu will only be available if reheat is enabled and the humidity contact is in dehumidify mode.

Reheat Interrupt Mode
Reheat operation will be interrupted if the temperature conditions are demanding heating or cooling operations in the default configuration. To enable reheat operation when there is heating demand, use the On Cool mode, which will only interrupt reheat when there is a cooling demand.

AGROWtEK Temperature Humidity Controller - Reheat Interrupt Mode

Modua Deskribapena
Lehenetsia Interrupt reheat if heating or cooling is demanded.
On Cool Interrupt reheat only if cooling is demanded.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
This menu will only be available if reheat is enabled.

Heat Pump Reversing Valve
Systems configured for heat pumps must specify whether the reversing valve contact (W1) should operate with the heating or cooling demand.

AGROWtEK Temperature Humidity Controller - Heat Pump Reversing Valve

Modua Deskribapena
Bero On Operate the valve with the heating demand.
On Cool Operate the valve with the cooling demand.

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
This menu will only be available if the System Type is set to Heat Pump.

Hezetasun modua
The humidity contact (HUM) can be configured to operate in humidify or dehumidify mode. Select the mode according to the type of equipment connected to the humidity contact (humidifier or dehumidifier)

AGROWtEK Temperature Humidity Controller - Humidity Mode

Modua Deskribapena
Dehum Operate dehumidification equipment.
Hum Operate humidification equipment.

Fan Atzerapena
The fan delay will operate the HVAC system fan contact for a period following the end of the heating or cooling signals to improve the efficiency of the system.

AGROWtEK Temperature Humidity Controller - Fan Delay

Denbora Aukerak (segundoak)
0, 30, 60, 90

Konpresorearen atzerapena
The compressor delay will inhibit the operation of the HVAC system compressors for a period following their shutdown to prevent short-cycling.

AGROWtEK Temperature Humidity Controller - Compressor Delay

Denbora Aukerak (segundoak)
0, 60, 120, 180, 240, 300

LCD Timeout
Set the timeout for the LCD to turn off the backlight.

AGROWtEK Temperature Humidity Controller - LCD Timeout

Denbora Aukerak (segundoak)
5-30

Unitateak
Select °F or °C units for temperature display and set points.
AGROWtEK Temperature Humidity Controller - UnitsTo modify the units selection, press the Enter button, then use the up or down buttons to toggle between the units. Press the Enter button to confirm once the desired units are displayed.

Gailuaren helbidea

Ezarri Helbidea
The device address is an internal number that the GCX control system uses to communicate with the THC. The address can be manually modified to a specific value, or set the value to ‘NONE.’

AGROWtEK Temperature Humidity Controller - Set Address

AGROWtEK Temperature Humidity Controller - Symbol 1 OHARRA
To ‘reset’ the THC and make it automatically discoverable by a GCX system, set the address to ‘NONE.’

Device Info Menu
The Device Info menu is located within the Config Menu and contains information about the device, including the serial number, hardware and firmware versions, and date of manufacture.

AGROWtEK Temperature Humidity Controller - Device Info Menu

Gailuaren helbidea
The device address that is in the system memory is displayed here.

AGROWtEK Temperature Humidity Controller - Device Address

Serie zenbakia
The device serial number is displayed here.

AGROWtEK Temperature Humidity Controller - Serial Number

Fabrikazio data
The date that the device was manufactured is displayed here.

AGROWtEK Temperature Humidity Controller - Date of Manufacture

Hardware bertsioa
The device hardware version number is displayed here.

AGROWtEK Temperature Humidity Controller - Hardware Version

Firmware bertsioa
The firmware version that is installed on the device is displayed here.

AGROWtEK Temperature Humidity Controller - Firmware Version

GrowControl™ GCX-ra konektatzea

GrowNET™ gailu guztiak RJ-5 konexiodun CAT45 Ethernet kable estandarraren bidez konektatuta daude.

Devices can be connected directly to the GrowNET™ ports on the bottom of the controller, or through HX8 GrowNET™ hubs. It is typical to simplify cabling by locating hubs centrally in hallways and rooms, allowing single runs from an 8-port device hub back to a central hub or back to the controller.

AGROWtEK Temperature Humidity Controller - Connection to GrowControl™ GCX

Ikusi GCX kontroladorearen eskuliburua gailua sistemara gehitzeko xehetasunak lortzeko.

GrowNET™ zentroak

HX8 GrowNET ™ zentroek portu bakar bat zabaltzen dute beste zortzi ataketan.
Hubak margarita kateatu daitezke GrowNET™ autobus bakoitzeko 100 gailuko sarea osatzeko. Banaka bufferatutako portu-transceptoreek seinalearen osotasun bikaina eta komunikazio-indarra eta zabalera zabala eskaintzen dute.

AGROWtEK Temperature Humidity Controller - GrowNET™ Hubs

Zentroek 1A-ko potentzia ematen dute sentsoreak eta errele gehienek zuzenean CAT5 kablearen gainean. Zentroko DC jack batek 24Vdc-ko energia ematen die portuei hormako horma-iturritik. Terminal-blokearen energia-aukera bat ere eskuragarri dago.

Easy THC Configuration

GrowControl™ GCX control systems integrate seamlessly with the THC.
Manage all of the configuration options from the controller without having to navigate the LCD menus.
See the ‘Open Device Configuration ‘ button on the ‘Device Info’ tab when monitoring the THC from a GCX system.

AGROWtEK Temperature Humidity Controller - Easy THC Configuration

Monitoring & Logging
Monitor and log the data from the THC in real time; receive alerts and review sistemaren errendimendua.
The GCX can also manually override the contacts on the THC for maintenance or testing.

AGROWtEK Temperature Humidity Controller - Monitoring & Logging

Automatic Settings Changes

The GCX system can automate changes to the set points by configuring ‘HVAC’ function blocks.
The function blocks can contain any number of ‘rules,’ each rule containing its own set of points. The rules can then be activated based on the growing schedule.
When a rule is activated with settings that differ from those stored in the THC, the new settings are transmitted to the THC for use.

AGROWtEK Temperature Humidity Controller - Automatic Settings Changes

Biltegiratzea eta botatzea

Biltegiratzea
Gorde ekipoak ingurune garbi eta lehor batean, 10-50 °C arteko giro-tenperaturan.

Ezabatzea
This industrial control equipment may contain traces of lead or other metals and environmental contaminants and must not be discarded as unsorted municipal waste, but must be collected separately for the purpose of treatment, recovery, and environmentally sound disposal. Wash your hands after handling internal components or PCBs.

Bermea

Agrowtek Inc. warrants that all manufactured products are, to the best of its knowledge, free of defective material and workmanship and warrants this product for one (1) year from the date of purchase. This warranty is extended to the original purchaser from the date of purchase. Returns not purchased directly from Agrowtek Inc. must include proof of purchase date; otherwise, the purchase date is considered the date of manu-facture. This warranty does not cover damages from abuse, accidental breakage, or items that have been modified, altered, or installed in a manner other than that which is specified in the installation instructions. This warranty is applicable only to products that have been properly stored, installed, and maintained per the installation and operation manual and used for their intended purpose. This limited warranty does not cover products installed in or operated under unusual conditions or environments, including, but not limited to, excessive humidity or extreme temperature conditions outside of the specified limits. Agrowtek Inc. must be contacted prior to the return shipment of any returns for a return authorization. No returns will be accepted without a return authorization. Customer is responsible for the return shipment to Agrowtek Inc. for warranty service. Return authorization number(s) must be printed on the outside of the box, or the return may be rejected and returned to the sender. Agrowtek Inc. is not responsible for supplying replacement products or parts in advance of return(s) for a warranty claim. The products that have been claimed and comply with the aforementioned restrictions shall be replaced or repaired at the sole discretion of Agrowtek Inc. at no charge. This warranty is provided in lieu of all other warranty provisions, express or implied. It includes, but is not limited to, any implied warranty of fitness or merchantability for a particular purpose and is limited to the Warranty Period. In no event or circumstance shall Agrowtek Inc. be liable to any third party or the claimant for damages in excess of the price paid for the product, or for any loss of use, inconvenience, com-mercial loss, loss of time, lost profits or savings or any other incidental, consequential or special damages arising out of the use of, or inability to use, the product. This disclaimer is made to the fullest extent allowed by law or regulation and is specifically made to specify that the liability of Agrowtek Inc. under this limited warranty, or any claimed extension thereof, shall be to replace or repair the Product or refund the price paid for the Product.

Š Agrowtek Inc.
| www.agrowtek.com
| Hazten lagunduko dizun teknologia™

Dokumentuak / Baliabideak

PDF thumbnailTenperatura Hezetasun Kontrolatzailea
Instruction Manual ¡ IM_THC.pdf, Temperature Humidity Controller, Humidity Controller, Controller

Galdera bat egin

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Galdera bat egin

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.