Eltako ES12Z-200

Eltako ES12Z-200 Bulkada-errele modularraren erabiltzailearen eskuliburua

Model: ES12Z-200 | Brand: Eltako

1. Sarrera

The Eltako ES12Z-200 is a modular impulse relay designed for inline installation on a DIN-EN 50 022 rail. This device features galvanically isolated working contacts and centralized control inputs, allowing for local control with a different phase and voltage than the centralized system. It includes a rotary switch for setting different priorities between control inputs and determining the device's behavior (switch off or maintain position) after a power failure.

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Eltako ES12Z-200 impulse relay.

2. Ezaugarri nagusiak

  • Modular design for DIN rail mounting (1 module unit = 18mm wide).
  • Wide control voltage range: 8 to 230 V AC/DC.
  • Galvanically isolated control inputs for flexible local and centralized control.
  • Integrated rotary switch for priority selection and power failure behavior.
  • Two normally open (NO) contacts.
  • Rated current: 16 A.

3. Zehaztapen Teknikoak

ZehaztapenaBalioa
FabrikatzaileaEltako
Modelo zenbakiaES12Z-200 (21200601)
Muntatze MotaDIN erraila
Width in Module Units1 (18 mm)
Number of Normally Open Contacts (NO)2
Kontrol boltage Barrutia8tik 230 V AC/DC
Korronte nominatua16 A
Funtzionamendu moduaPIZTU ITZALI
Produktuaren neurriak (L x W x H)9.5 x 6 x 2.5 cm
Pisua70 gramo
MaterialaNeon (for indicator lamp)
Ordezko piezen erabilgarritasunaInformazioa ez dago eskuragarri

4. Segurtasun informazioa

WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified electricians in accordance with all national and local electrical codes and regulations.

  • Deskonektatu beti korrontea gailua instalatu, konpondu edo kendu aurretik.
  • Ziurtatu lurrerako konexioak eta kableatu konexioak behar bezala daudela.
  • Ez gainditu zehaztutako bolumenatage eta egungo balorazioak.
  • Babestu gailua hezetasunetik, hautsetik eta muturreko tenperaturetatik.
  • Egiaztatu konexio guztiak seguru daudela argindarra berrezarri aurretik.

5. Instalazioa

5.1 Muntaketa

The Eltako ES12Z-200 is designed for mounting on a standard DIN-EN 50 022 rail. Ensure sufficient space for ventilation and access to terminals.

5.2 Kableatu-diagrama

Refer to the wiring diagram below for correct electrical connections. The device supports both local and centralized control inputs with galvanic isolation.

Wiring diagram for Eltako ES12Z-200 impulse relay showing connections for L, N, control inputs (local, central on, central off), and output contacts.

1. irudia: Wiring diagram for the Eltako ES12Z-200 impulse relay. This diagram illustrates the connections for the main power supply (L, N), local control input, centralized control inputs (central on, central off), and the output contacts (1, 2). It also shows the internal circuitry for the control voltage and the 16A/250V output rating.

5.3 Konexio-urratsak

  1. Elikatze-iturria: Connect the live (L) and neutral (N) wires to the designated terminals as shown in the diagram. The device operates with a supply voltage range of 8-230V AC/DC.
  2. Kontrol lokala: Connect your local push-button or switch to the 'local on/off' input. This input typically requires a control current of up to 150mA for neon lamps from 110V.
  3. Kontrol zentralizatua: Connect centralized 'on' and 'off' control signals to the respective terminals. These inputs are galvanically isolated, allowing for different control voltages edo faseak.
  4. Irteerako kontaktuak: Connect the load (e.g., lighting circuit) to the output contacts (1 and 2). The relay provides two normally open (NO) contacts with a maximum current rating of 16A at 250V.
  5. Egiaztapena: Double-check all connections for correctness and security before applying power.

6. Funtzionamendua

6.1 Oinarrizko funtzionalitatea

The Eltako ES12Z-200 functions as an impulse relay. A brief pulse to any activated control input (local, central on) will toggle the state of the output contacts. A pulse to the central off input will switch the contacts to the OFF state.

6.2 Priority Selection and Power Failure Behavior

The device features a rotary switch on its front panel to configure priority settings for control inputs and define behavior during power failures.

Close-up of the Eltako ES12Z-200 rotary switch for priority selection and power failure settings.

2. irudia: Gertutik view of the Eltako ES12Z-200 rotary switch. This switch allows users to select different priority levels for control inputs and configure the relay's response to power outages, such as switching off or maintaining its current state.

The rotary switch allows you to:

  • Set different priority levels for the various control inputs (e.g., local vs. centralized).
  • Determine the relay's state after a power failure: either switch off or maintain its last switching position upon power return. Consult the specific markings on your device for detailed settings.

7. Mantentzea

The Eltako ES12Z-200 impulse relay is designed for long-term, maintenance-free operation under normal conditions. However, periodic checks are recommended:

  • Ikus-ikuskapena: Periodically inspect the device for any signs of physical damage, overheating, or loose connections.
  • Garbiketa: If necessary, gently clean the exterior of the device with a dry, soft cloth. Do not use liquid cleaners or solvents.
  • Terminalaren estutasuna: Ensure all terminal screws remain tight to prevent poor contact and potential overheating.

Always disconnect power before performing any inspection or cleaning.

8. Arazoak

If you encounter issues with your Eltako ES12Z-200, refer to the following table for common problems and solutions:

ArazoaKausa posibleaIrtenbidea
Relay does not respond to control input.No power supply; incorrect wiring; faulty control switch; control voltage outside range.Check power supply to L and N terminals. Verify all wiring connections against the diagram. Test the control switch. Ensure control voltage is within 8-230V AC/DC.
Load does not switch ON/OFF.Faulty load; incorrect load wiring; overloaded contacts.Check the load (e.g., light bulb). Verify wiring to output contacts. Ensure load current does not exceed 16A.
Relay switches erratically.Interference; loose connections; faulty device.Check for sources of electrical interference. Tighten all terminal connections. If problem persists, the device may be faulty and require replacement.
Device gets excessively hot.Overloaded contacts; poor ventilation; loose connections.Reduce load if exceeding 16A. Ensure adequate ventilation around the device. Tighten all connections.

9. Bermea eta Laguntza

Information regarding a manufacturer's warranty for the Eltako ES12Z-200 is not explicitly provided. This product may be subject to the terms of a private sale without warranty, as indicated in some product descriptions. Additionally, information on the availability of spare parts is not available.

For any warranty claims or technical support, please contact your point of purchase or the seller directly. They can provide details on applicable return policies or support options.

10. Produktuaren neurriak

The Eltako ES12Z-200 is a compact device, designed to fit within standard electrical enclosures.

Image showing the Eltako ES12Z-200 impulse relay held in a hand, illustrating its compact size with dimensions of 2.6 inches (6 cm) in height.

3. irudia: The Eltako ES12Z-200 impulse relay shown in hand, providing a visual reference for its compact dimensions. The image highlights a height of approximately 2.6 inches (6 cm).

Erlazionatutako dokumentuak - ES12Z-200

Aurreview Eltako SU12DBT/1+1-UC: 2 kanaleko Bluetooth tenporizadorea pantaila eta aplikazio bidezko kontrolarekin
Arakatu Eltako SU12DBT/1+1-UC, pantaila, Bluetooth eta ELTAKO Connect-App integrazioarekin dituen 2 kanaleko tenporizadore polifazetikoa. 16A/250V AC kontaktua, funtzio astroa eta DIN errail muntaketa ditu kontrol elektriko eraginkorra lortzeko.
Aurreview Eltako S2U12DDX-UC Digital Timer with Display: User Manual and Technical Specifications
Comprehensive guide to the Eltako S2U12DDX-UC digital timer, covering installation, programming, features like astro function, summer/winter time changeover, and technical data. Includes wiring diagrams and program examples.
Aurreview Eltako SU12DBT/1+1-UC 2-Channel Bluetooth Timer: User Manual and Technical Specifications
Comprehensive guide for the Eltako SU12DBT/1+1-UC 2-channel timer with Bluetooth. Learn about installation, setup, programming, features like astro function, and technical data.
Aurreview Eltako TLZ12-8plus Eskailera Argiaren Tenporizadore Etengailua - Ezaugarri Teknikoak eta Instalazio Gida
Comprehensive guide to the Eltako TLZ12-8plus staircase light timer switch, covering its features, technical specifications, multi-functionality, connection diagrams, and installation notes for optimal lighting control. Includes detailed explanations of functions like switch-off warning and push-button continuous light.
Aurreview Eltako ESR12NP-230V+UC Inpultso Etengailua Errele Funtzio Integratuarekin
Technical specifications and operating instructions for the Eltako ESR12NP-230V+UC impulse switch with integrated relay function. Details on installation, functions, technical data, and wiring.
Aurreview Eltako MFZ12DX-UC Denbora Errele Multifuntzionala - Erabiltzailearen Gida
Eltako MFZ12DX-UC denbora-errele multifuntzionala doitzeko analogikoaren gida osoa, bere 18 funtzioak, zehaztapen teknikoak eta konexio-exekuzioak zehaztuz.amples.