This manual provides detailed instructions for the installation, operation, and maintenance of the Intermatic T1906 SPDT 24-Hour Time Switch. Please read all instructions carefully before installation and use to ensure proper function and safety.

Segurtasun informazio garrantzitsua:

  • Always disconnect power at the circuit breaker before installing or servicing the time switch.
  • Instalazioa elektrizista kualifikatu batek egin behar du, tokiko eta estatuko arau elektriko guztien arabera.
  • This device is designed for indoor use within a 3R steel enclosure.

Produktua amaituview

The Intermatic T1906 is a robust 24-hour time switch designed for automatic control of electrical loads. It features a single-pole, double-throw (SPDT) switch and operates on 208-277 Volts. Key features include:

  • Up to 96 operations (48 ON/48 OFF) every 24 hours.
  • 15-minute minimum ON/OFF intervals.
  • Captive trippers for easy setting.
  • Suitable for applications requiring daily repetitive scheduling.

Instalazioa

Segurtasun-neurriak

  • Ensure power is OFF at the main service panel before beginning installation.
  • Egiaztatu voltage supply matches the time switch rating (208-277V).
  • Ground the enclosure properly.

Muntaketa

  1. Select a suitable indoor location for the 3R steel enclosure, protected from direct weather and excessive moisture.
  2. Mount the enclosure securely using appropriate fasteners through the pre-drilled holes.

Kableatua

Refer to the wiring diagram provided inside the enclosure cover. The T1906 is an SPDT switch, meaning it has one common terminal and two switched terminals (normally open and normally closed).

  1. Konektatu sarrerako linea voltage to the designated line terminal.
  2. Connect the load(s) to the appropriate switched terminals (NO or NC) and the neutral/return line.
  3. Ziurtatu konexio guztiak estu eta seguru daudela.
  4. KONTUZ: Make sure non-operating trippers (if any) clear the switch lever.
  5. GARRANTZITSUA: The insulator must be replaced after wiring to prevent shock.
Intermatic T1906 Time Switch internal view showing the 24-hour dial with captive trippers and warning labels.

1. irudia: Barnekoa view of the Intermatic T1906 Time Switch. This image displays the 24-hour clock dial with numerous small, gold-colored captive trippers around its circumference. A central silver hand indicates the current time. Below the dial, a translucent plastic insulator covers wiring terminals, with a warning label visible: "CAUTION: MAKE SURE NON-OPERATING TRIPPERS (IF ANY) CLEAR SWITCH LEVER" and "THIS INSULATOR MUST BE REPLACED AFTER WIRING TO PREVENT SHOCK."

Funtzionamendu-argibideak

Ordua ezartzea

  1. Biratu diala clockwise only until the current time aligns with the time indicator arrow. The dial is marked with AM and PM hours.

Setting ON/OFF Times

The T1906 uses captive trippers around the dial to set ON and OFF times. Each tripper represents a 15-minute interval.

  1. To set an ON period, push the trippers outwards for the desired duration.
  2. To set an OFF period, leave the trippers in their inward position for the desired duration.
  3. Ensure that the trippers are firmly set in their respective positions (in or out).
  4. For models with a skipper wheel (if applicable), operations can be omitted on selected days of the week. Refer to the specific instructions for skipper wheel adjustment if your model includes this feature.

Eskuzko gainidaztea

The time switch may include a manual override lever. Consult the specific product diagram for its location and operation. This allows for temporary ON/OFF control without affecting the programmed schedule.

Mantentzea

  • The Intermatic T1906 is designed for minimal maintenance.
  • Periodically inspect the enclosure for any signs of damage or corrosion.
  • Ziurtatu kableatu-konexio guztiak ondo finkatuta daudela.
  • Keep the internal components free from dust and debris.
  • Do not lubricate any internal parts.

Arazoak konpontzea

ArazoaKausa posibleaIrtenbidea
Time switch does not operate.No power supply; incorrect wiring; faulty motor.Check circuit breaker and power connections. Verify wiring against diagram. If motor is faulty, contact Intermatic support.
Load does not turn ON/OFF at programmed times.Trippers incorrectly set; time dial not set to current time; faulty switch mechanism.Ensure trippers are pushed in/out firmly. Verify current time setting. Check for obstructions to the switch lever.
Motor hums but dial does not turn.Obstruction in gear train; motor issue.Disconnect power and inspect for obstructions. If problem persists, contact Intermatic support.

If troubleshooting steps do not resolve the issue, contact Intermatic customer support or a qualified electrician.

Zehaztapenak

  • Eredua: T1906
  • Mota: 24-Hour SPDT Time Switch
  • liburukiatage: 208-277 volt
  • Itxitura: 3R Indoor Steel Enclosure
  • Neurriak (Produktua): 5.5 x 3.5 x 8.25 hazbete inguru
  • Pisua: 2 kilo inguru
  • Maximum Operations: 96 (48 ON / 48 OFF) per 24 hours
  • Gutxieneko PIZTE/ITZALTZE denbora: 15 minutu
  • Materiala: Altzairua
  • Ziurtagiria: CSA (Canada and US)

Bermearen informazioa

For detailed warranty information, please refer to the manufacturer's official documentation or visit the Intermatic webgunea. Berme-baldintzek normalean materialen eta fabrikazioaren akatsak estaltzen dituzte erosketa-datatik aurrerako denbora-tarte jakin batean.

Bezeroarentzako Arreta

For technical assistance, replacement parts, or further inquiries, please contact Intermatic customer support. You can find contact information on the official Intermatic webgunea edo zure produktuen saltzailearen bidez.

Intermatic Webgunea: www.intermatic.com

Erlazionatutako dokumentuak - T1906

Aurreview Intermatic T105 24-Hour Dial Time Switch: Installation, Wiring, and Operation Guide
Comprehensive guide for the Intermatic T105 24-hour mechanical dial time switch. Covers model specifications, safety warnings, wiring instructions for various configurations (SPNO, SPNC, SPDT), programming procedures, and manual operation. Includes a detailed table of electrical ratings and wire gauge recommendations.
Aurreview Intermatic Spring Wound Interval Timer Installation and Operation Guide
Detailed installation, operation, and application guide for Intermatic spring wound interval timers (FF and FD models). Includes switch ratings, wiring diagrams, and warranty information.
Aurreview Intermatic GMXFM1 Electronic Time Switch Instruction Manual
Instruction manual for the Intermatic GMXFM1 electronic time switch, covering safety precautions, symbols, initial setup, programming, time settings, daylight saving adjustments, operating modes, and warranty information.
Aurreview Intermatic EJ351 Barruko Hormako Etengailu Tenporizadorea: Instalazio, Programazio eta Arazoak Konpontzeko Gida
Intermatic EJ351 Barruko Hormako etengailu-tenporizadorea instalatzeko, programatzeko eta arazoak konpontzeko gida osoa. Ikasi ordutegiak nola ezarri, modu automatikoak eta eskuzkoak nola erabili eta ohiko arazoak nola konpondu.
Aurreview Intermatic KM2 Serieko Hormako Tenporizadorea: Instalazio eta Erabilera Argibideak
Intermatic KM2 Serieko Hormako Tenporizadoreak instalatzeko eta erabiltzeko gida osoa. Ikasi argiztapena eta beste zirkuitu batzuk automatikoki kontrolatzeko ezaugarriak, zehaztapenak, programazioa eta kableatua.
Aurreview Intermatic ET8215C Electronic Timer Control - Technical Data
Detailed technical specifications for the Intermatic ET8215C Electronic Timer Control, an astronomic 7-day, 2-circuit electronic control suitable for 120-277 VAC applications in an indoor metal enclosure.