SmartGen HAT560NB

SmartGen HAT560NB ATS Controller User Manual

1. Sarrera

The SmartGen HAT560NB ATS Controller is an intelligent dual-supply module designed for Automatic Transfer Systems (ATS). It integrates digital, intelligent, and networked functionalities to provide precise voltage measurement and control for various power supply configurations. This controller is suitable for specialized ATS, Contactor ATS, and Air Break ATS applications, offering a compact structure, advanced circuitry, and high reliability.

It is engineered to reduce operational errors through automatic measurement and control, making it an ideal solution for managing power transfer between different sources like mains and generators.

SmartGen HAT560NB ATS Controller front view with LCD display and control buttons

1. irudia: Aurrealdea view of the SmartGen HAT560NB ATS Controller, showing the LCD display and operational buttons.

2. Features and Characteristics

The HAT560NB controller incorporates a powerful microprocessor for accurate monitoring and control. Key features include:

  • System type configuration: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#).
  • 132x64 LCD with backlight, offering optional Chinese and English display with push-button operation.
  • Measurement and display of 2-way 3-phase voltage eta maiztasuna.
  • Vol. gehiegi/azpitik babesteatage, loss of phase, reverse phase sequence, and over/under frequency.
  • Automatic and Manual operating modes. Manual mode allows forced switch closure or opening.
  • All parameters are configurable on-site, secured by two different passwords for authorized access.
  • Genset commissioning can be set to On-load or Off-load mode.
  • Automatic re-closing function for the ATS Controller.
  • Configurable closing output signal as either on intervals or continuous output.
  • Applicable for ATS with one neutral position, two neutral positions, and non-position types.
  • Monitors 1-3 phase AC mains voltages.
  • Manages changeover of both generator and mains contactors.
  • Sends remote start commands to the generating set.
  • Compatible with various contactors and changeover switch types.

3. Konfigurazioa eta instalazioa

Proper installation is crucial for the safe and reliable operation of the HAT560NB controller. Ensure all power is disconnected before beginning installation. Refer to the wiring diagrams and terminal descriptions for correct connections.

3.1 Kableatu-diagramak

The HAT560NB controller supports various wiring configurations depending on the ATS type. Below are typical wiring diagrams for different setups. Always consult a qualified electrician for installation.

Multiple wiring diagrams for ATS controllers including ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG types

Figure 2: Comprehensive wiring diagrams illustrating connections for ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG ATS controller types. These diagrams show connections for 1# and 2# power supplies, load, and remote start signals.

Detailed wiring diagrams for SGQ-N/T, SGQ-M, and Contactor ATS configurations

Figure 3: Additional wiring diagrams focusing on SGQ-N/T, SGQ-M, and Contactor ATS configurations, detailing input and output connections for the controller.

3.2 Connecting Terminals

The controller features clearly labeled terminals for power input, auxiliary outputs, and control signals. Ensure each wire is securely connected to its designated terminal.

Atzekoa view of the HAT560NB controller showing labeled connecting terminals for inputs and outputs

4. Irudia: Atzealdea view of the HAT560NB controller, displaying the layout and labeling of all connecting terminals, including power inputs, auxiliary outputs, and communication ports.

4. Funtzionamendu-argibideak

The HAT560NB controller offers both automatic and manual operation modes, accessible via its front panel buttons and LCD display.

4.1 Piztea eta hasierako pantaila

Upon powering on, the LCD will display system information, including voltage and frequency readings for both power sources. The backlight ensures visibility in various lighting conditions.

4.2 Modu hautaketa

  • Modu automatikoa: The controller automatically monitors the power sources and initiates transfer based on pre-set parameters and detected abnormalities (e.g., over/under voltage, frequency deviations, phase loss).
  • Eskuzko modua: Allows the user to manually control the opening or closing of the transfer switches. This mode is typically used for testing or specific operational requirements.

4.3 Parametroen ezarpena

All operational parameters can be configured directly on the unit using the push-buttons and LCD interface. Access to parameter settings is protected by a two-level password system to prevent unauthorized changes. Refer to the detailed programming guide (not included in this manual) for specific parameter definitions and adjustment procedures.

5. Mantentzea

Regular maintenance ensures the longevity and reliable performance of your HAT560NB ATS Controller.

  • Garbiketa: Keep the controller's exterior clean and free from dust and debris. Use a soft, dry cloth. Avoid abrasive cleaners or solvents.
  • Konexioaren egiaztapenak: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to intermittent operation or system failures.
  • Ingurumen-baldintzak: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage to internal components.

For any internal maintenance or repairs, contact qualified service personnel.

6. Arazoak

This section provides guidance on common issues you might encounter with the HAT560NB controller.

ArazoaKausa posibleaIrtenbidea
Kontrolagailua ez da piztenNo DC power supply; Incorrect wiringCheck DC 8.0V-35.0V power supply connections; Verify wiring according to diagrams.
ATS not transferring automaticallyAutomatic mode not selected; Fault detected on active power source (e.g., over/under voltage, frequency); Incorrect parametersEnsure controller is in Automatic mode; Check power source status; Verify parameter settings.
Display shows error for voltage / maiztasunaActual power source issue; Sensor/input wiring problemEgiaztatu benetako bolumenatage and frequency of the power source; Inspect AC voltage sarrerako kableatua.
Botoiek ez dute erantzutenTemporary software glitch; Hardware issueRestart the controller by cycling power; If issue persists, contact support.

7. Zehaztapenak

The following table details the technical specifications for the SmartGen HAT560NB ATS Controller.

Table of specifications for SmartGen HAT560N series ATS Controller

Figure 5: Detailed specifications table for the HAT560N series ATS Controller, including operating voltage, power consumption, AC voltage input ranges, rated frequency, relay outputs, communication, dimensions, and environmental conditions.

ElementuaZehaztapena
Bolumen eragileatageDC 8.0V-35.0V (continuous power supply)
AC Boltage SarreraAC170V-270V (during AC power L1N1/L2N2 supply)
Energia-kontsumoa<3W (Itxaroteko modua: <2W)
Maiztasun baloratua50/60Hz
Itxi errele irteera16A AC250V (Volts free output)
Errele laguntzailearen irteera 17A AC250V (Volts free output)
Errele laguntzailearen irteera 27A AC250V (Volts free output)
Errele laguntzailearen irteera 316A AC250V (Volts free output)
Errele laguntzailearen irteera 416A AC250V (Volts free output)
Sarrera digitalaGND connect is active
KomunikazioaLINK interfazea, MODBUS protokoloa
Kasuen neurriak139 mm x 120 mm x 48 mm (5.47 x 4.72 x 1.89 hazbete)
Panelaren mozketa130 mm x 111 mm
Lan BaldintzakTemperature: (-25~+70)°C, Humidity: (20~93)%RH
Biltegiratze-baldintzaTenperatura: (-25~+70)°C
Babes MailaIP55 junta
Isolamendu-indarraAplikatu AC2.2kV boltage bolumen handiko arteantage terminala eta bolumen baxuatage terminala; Ihes-korrontea ez da 3mA baino gehiago 1min barruan.
Pisua0.62 kg (1.63 libra)

Erlazionatutako dokumentuak - HAT560NB

Aurreview HAT72 ATS kontrolagailuaren erabiltzailearen eskuliburua
Smartgen HAT72 Transferentzia Automatikoko Kommutadore (ATS) kontrolatzailearen erabiltzailearen eskuliburua, non bere ezaugarriak, parametro teknikoak, funtzionamendua, terminalen konexioak eta sare elektrikoaren eta sorgailuaren potentzia-aldaketaren ohiko kableatua zehaztuta dauden. Potentzia-transferentzia automatiko fidagarria lortzeko diseinatua.
Aurreview SmartGen HAT520N ATS kontrolagailuaren erabiltzailearen eskuliburua
User manual for the SmartGen HAT520N Dual Power ATS Controller, detailing its performance, specifications, panel operations, parameter configuration, installation, and troubleshooting.
Aurreview SmartGen HAT530N ATS kontrolagailuaren erabiltzailearen eskuliburua
This user manual provides comprehensive instructions and specifications for the SmartGen HAT530N ATS Controller. Learn about its features, operation, parameter settings, wiring diagrams, and troubleshooting.
Aurreview SmartGen HAT880 Serieko Bi Potentzia Bypass ATS Kontrolagailuaren Erabiltzaile Eskuliburua
Erabiltzailearen eskuliburu honek SmartGen HAT880 Serieko Energia Bikoitzeko Bypass ATS Kontrolagailuaren (HAT880/HAT880S) funtzionamendu eta teknika gida zehatza eskaintzen du, eta ezaugarriak, zehaztapenak, funtzionamendua, instalazioa eta energia bikoitzeko kudeaketa fidagarria lortzeko arazoak konpontzea azaltzen ditu.
Aurreview SmartGen HAT520N Transferentzia Automatikoko Etengailuaren (ATS) Erabiltzailearen Eskuliburua eta Zehaztapenak
SmartGen HAT520N Transferentzia Automatikoko (ATS) kontrolatzailearen erabiltzailearen eskuliburu osoa eta zehaztapen teknikoak, hainbat elikatze-iturri konfigurazioren funtzionamendua, segurtasuna, instalazioa eta arazoak konpontzea barne hartzen dituena.
Aurreview SmartGen HAT520NC ATS kontrolagailuaren erabiltzailearen eskuliburua
User manual for the SmartGen HAT520NC Automatic Transfer Switch (ATS) Controller, detailing its features, specifications, panel operations, wiring, installation, and troubleshooting.