Elitech VG-760

Elitech VG-760 HVAC mikroi-hutsune-neurgailu digitalaren instrukzio-eskuliburua

1. Sarrera

This manual provides detailed instructions for the proper use, setup, operation, maintenance, and troubleshooting of the Elitech VG-760 Digital HVAC Micron Vacuum Gauge. This device is designed for accurate vacuum measurement in HVAC and refrigeration systems, ensuring efficient and reliable performance.

The Elitech VG-760 is a robust digital vacuum gauge featuring a wide measurement range, high accuracy, and multiple measurement units. It is built with an IP65 rating for enhanced protection against environmental factors.

2. Segurtasun informazioa

  • Always wear appropriate personal protective equipment (PPE) when working with HVAC/R systems.
  • Ensure the system is depressurized before connecting or disconnecting the vacuum gauge.
  • Do not expose the gauge to extreme temperatures or corrosive substances.
  • Handle the gauge with care to prevent damage to the sensor.
  • Mantendu gailua haurrengandik urrun.

3. Produktua amaitu daview

The Elitech VG-760 Digital HVAC Micron Vacuum Gauge is designed for precise vacuum measurement. Its compact design and clear display make it suitable for various applications.

Elitech VG-760 Digital Vacuum Gauge

Figure 1: Elitech VG-760 Digital Vacuum Gauge, showing its compact design and digital display.

3.1 Ezaugarri nagusiak

  • Wide Measurement Range: 0-19000 Microns.
  • High Accuracy: ±10% or ±10 Micron.
  • Multiple Measurement Units: inHg, Torr, psi, mbar, mTorr, Pa, micron, Kpa.
  • Settable High/Low Pressure Alarms.
  • IP65 Rated for enhanced protection.
  • Long Battery Life: Up to 300 hours with 3 AA batteries.

3.2 Display and Button Functions

Elitech VG-760 display and button functions

Figure 2: Elitech VG-760 display elements and button controls. 1. Battery Level, 2. Auto OFF (15 min), 3. Current Vacuum Value, 4. Units. Buttons: A (Backlight on/off), B (Power on/off), C (Switch units). Pressing A+B enables auto-off.

Elitech VG-760 display showing 8 units

Figure 3: The Elitech VG-760 supports 8 different measurement units: inHg, Torr, psia, mbar, mTorr, Pa, micron, and kPa.

3.3 Filtering Components

Elitech VG-760 multiple filtering components

4. Irudia: Lehertuta view of the Elitech VG-760's multiple filtering system, including the O-ring, Filter Net, Filter Cotton, and 1/4" SAE Fitting, designed to protect the sensor from contaminants.

4. Konfigurazioa

4.1 Paketatzea

Upon receiving your Elitech VG-760, carefully unpack all components. The packing list typically includes:

Elitech VG-760 packing list and contents

Figure 5: Contents of the Elitech VG-760 package, including the vacuum gauge, user manual, AA batteries, zip bag, filter cotton, filter net, and O-rings.

  • 1 x Vacuum Gauge
  • 1 x Erabiltzailearen eskuliburua
  • 3 x AA pila
  • 1 x Zip Bag
  • 2 x Filter Cotton & Filter Net
  • 2 x O-eraztun

4.2 Bateriaren instalazioa

  1. Locate the battery compartment on the back of the gauge.
  2. Ireki konpartimenduaren estalkia.
  3. Sartu 3 AA bateria, polaritate zuzena ziurtatuz.
  4. Itxi bateriaren konpartimenduaren estalkia ondo.

4.3 Connecting to the System

The VG-760 features a 1/4" SAE male flare fitting for connection to HVAC/R systems. Ensure all connections are tight to prevent leaks.

Video 1: Demonstrates how to connect the Elitech VG-760 to an HVAC system using a T-connector and bend adapter for vacuum measurement. It highlights the oil-proof film protection on the sensor and the process of attaching the gauge to a vacuum pump.

  1. Attach the VG-760 to the system using appropriate fittings (e.g., T-connector and bend adapter).
  2. Ensure the connection is secure and leak-free.

5. Funtzionamendu-argibideak

5.1 Piztu/Itzali

Sakatu Boterea button (center button) to turn the gauge on or off.

5.2 Atzeko argiaren kontrola

Sakatu Atzeko argia button (left button) to toggle the display backlight on or off for improved visibility in various lighting conditions.

5.3 Neurketa-unitateak aldatzea

Sakatu UNITATEAK button (right button) to cycle through the available measurement units: inHg, Torr, psi, mbar, mTorr, Pa, micron, and Kpa.

5.4 Auto-off funtzioa

The gauge features an auto-off function to conserve battery life. To enable or disable this feature, press and hold both the Atzeko argia eta Boterea botoiak aldi berean.

5.5 Interpreting Readings

The gauge displays the vacuum value in real-time. If the display shows dashes (-----), it indicates that the current pressure exceeds the measurement range of the gauge (above 19,000 microns).

6. Mantentzea

6.1 Sentsoreen garbiketa

If the vacuum gauge sensor becomes contaminated with oil, it may display no value or inaccurate readings. In such cases, it is necessary to clean the vacuum sensor.

Video 2: Illustrates the importance of cleaning the vacuum sensor if it becomes contaminated with oil, as contamination can prevent accurate readings. The video shows how to access and clean the sensor using a solvent.

  1. Disconnect the gauge from the system.
  2. Carefully remove the 1/4" SAE fitting to expose the sensor.
  3. Use a suitable solvent (e.g., isopropyl alcohol) and a lint-free cloth or cotton swab to gently clean the sensor surface.
  4. Allow the sensor to dry completely before reassembling.
  5. Replace the O-ring, filter net, and filter cotton as needed to ensure proper sealing and filtration.

6.2 Arreta orokorra

  • Store the gauge in its protective zip bag when not in use.
  • Avoid dropping or subjecting the gauge to strong impacts.
  • Garbitu kanpoaldea leun batekin, damp oihal bat behar izanez gero. Ez erabili garbitzaile urratzailerik.

7. Arazoak

ArazoaKausa posibleaIrtenbidea
Gauge does not power onBateria hutsik edo gaizki instalatutaAldatu bateriak edo egiaztatu polaritatea
Display shows dashes (-----)Pressure is above 19,000 microns (out of range)Continue evacuation until pressure drops within range
Inaccurate or no readingContaminated sensor (oil, debris)Clean the vacuum sensor as per maintenance instructions
Inaccurate or no readingSystem leakCheck all connections for leaks and repair as necessary

8. Zehaztapenak

Elitech VG-760 dimensions and technical specifications

Figure 6: Elitech VG-760 dimensions and key technical specifications.

ParametroaBalioa
Produktuaren neurriak4.92 x 1.38 x 2.76 hazbete
Elementuaren pisua15.52 Ounces (0.6 lbs)
Elementuaren eredu-zenbakiaVG-760
Pilak3 AA bateria (barne)
FabrikatzaileaElitech
MaterialaPlastikoa
Neurketa-eremua0-19000 mikra
Zehaztasuna±10% or ±10 Micron
Funtzionamendu-tenperatura0 ° F ~ 140 ° F (-17.8 ° C ~ 60 ° C)
Egokitzea1/4" SAE Male Flare
Bateriaren iraupenaGehienez 300 ordu
Babes MailaIP65 baloratua

9. Bermearen informazioa

Elitech products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the warranty card included with your product or contact Elitech customer support. Keep your purchase receipt as proof of purchase for warranty claims.

10. Bezeroarentzako arreta

For technical assistance, troubleshooting, or any inquiries regarding your Elitech VG-760 Digital HVAC Micron Vacuum Gauge, please contact Elitech customer support.

  • Posta elektronikoko laguntza: Eskuragarri 24/7
  • Telefono-laguntza: Available for US customers

Please visit the official Elitech webgunea kontaktu-informazio eta laguntza-baliabide eguneratuenak lortzeko.

Erlazionatutako dokumentuak - VG-760

Aurreview Elitech MS-100 Kolektore Digitalaren Neurgailua: Ezaugarriak, Funtzionamendua eta Zehaztapenak
Elitech MS-100 kolektore digitalaren neurgailuaren gida osoa, ezaugarriak, funtzionamendu azkarra, zehaztapen teknikoak, neurriak eta HVAC eta hozte sistemetarako produktuaren xehetasunak biltzen dituena.
Aurreview Elitech MS Serieko kolektore digitaleko neurgailuaren erabiltzailearen eskuliburua
Elitech MS Serieko kolektore digitalaren neurgailuaren erabiltzailearen eskuliburua, produktuaren deskribapena, informazio orokorra biltzen dituena.view, botoien funtzioak, zehaztapenak, hasiera azkarreko gida, funtzionamendu-urratsak, aplikazio adimendunak eta mantentze-lanak.
Aurreview Elitech MS-100 PLUS Kolektore Digital Adimendunaren Neurgailua Erabiltzailearen Eskuliburua
Elitech MS-100 PLUS Smart Digital Manifold Gauge-aren erabiltzailearen eskuliburu osoa, produktuaren aurkezpena, segurtasun-argibideak eta abar biltzen dituena.view, botoien funtzioak, parametro teknikoak eta hozte eta HVAC sistemetarako funtzionamendu azkarreko gida.
Aurreview Elitech MS-100 Digital Multifold Gauge erabiltzailearen eskuliburua
Elitech MS-100 neurgailu digitalaren erabiltzailearen eskuliburua, non ezaugarriak, funtzionamendua, zehaztapenak eta mantentze-lanak zehaztuta dauden.
Aurreview Elitech MS-800 Serieko Kolektore Digitalaren Neurgailua Erabiltzailearen Eskuliburua eta Zehaztapenak
Elitech MS-800 Serieko kolektore digitalaren tresnaren erabiltzailearen eskuliburu osoa, produktuaren aurkezpena, segurtasun jarraibideak, ingurumenaren babesa, zehaztapen zehatzak eta presio eta tenperatura neurketetarako, euste presio probak eta HVAC eta hozte sistemetarako hozgarri kargatzeko funtzionamendu gida azkarrak biltzen dituena.
Aurreview Elitech MS-100 kolektore digitala: erabiltzailearen eskuliburua eta zehaztapenak
Elitech MS-100 kolektore digitalaren gida osoa, bere ezaugarriak, zehaztapen teknikoak, funtzionamendua, segurtasun-argibideak eta arazoak konpontzea azaltzen dituena. Ikasi gailua nola erabili presio eta tenperatura neurketetarako, ihes-probetarako, huts-prozesuetarako eta datuak erregistratzeko Elitech Tools aplikazioarekin.