1. Sarrera
This manual provides essential information for the safe and effective installation, operation, and maintenance of the Danfoss MCI 15 Motor Controller, model 037N0039. Please read this manual thoroughly before attempting to install or operate the device. Retain this manual for future reference.
2. Segurtasun informazioa
Beti bete segurtasun neurri hauek lesio pertsonalak edo ekipamenduari kalteak saihesteko:
- Instalazioa eta mantentze-lanak langile kualifikatuek bakarrik egin behar dituzte.
- Ziurtatu energia-iturria deskonektatuta dagoela kableatu edo mantentze-lanak egin aurretik.
- Verify all connections are secure and correctly wired according to the provided diagrams.
- Babestu gailua hezetasunetik, hautsetik eta muturreko tenperaturetatik.
- Do not operate the controller if it appears damaged.
3. Produktua amaitu daview
The Danfoss MCI 15 Motor Controller is designed for controlling motor speed and soft starting applications. It features robust construction with an integrated heat sink for efficient thermal management.




4. Zehaztapenak
Key technical specifications for the Danfoss MCI 15 Motor Controller:
| Parametroa | Balioa |
|---|---|
| Modelo zenbakia | MCI 15 (037N0039) |
| Korronte nominatua (Ie) | Max 15 A AC 53a |
| Kontrol boltage (Uc) | 24-480 V AC/DC |
| Bolumen eragileatage (Ue) | 380-480V 50/60Hz |
| Isolamendua Voltage (Ui) | 660V |
| Bultzada jasan Voltage (Uimp) | 4 kV |
| Produktuaren neurriak | 5 x 5 x 2 hazbete |
| Elementuaren pisua | 1.35 kilo |
| Materiala | Copper (heat sink) |
| Max Fuse | 50 A gL/gG |
| Overload Relay Trip Class | 10 |
| HP Rating (400-480V) | 10 HP |


5. Konfigurazioa eta instalazioa
5.1 Muntaketa
The Danfoss MCI 15 Motor Controller is designed for panel mounting. Ensure adequate ventilation around the heat sink to prevent overheating. Use appropriate fasteners through the mounting brackets shown in Figure 3.4.
5.2 Kableatua
Refer to the wiring diagram on the device label (Figure 4.1) for correct connections. Ensure all wiring adheres to local electrical codes and safety standards.
- Power Input (L1, L2, L3): Connect the three-phase power supply to terminals 1/L1, 3/L2, and 5/L3.
- Motor Output (T1, T2, T3): Connect the motor leads to terminals 2/T1, 4/T2, and 6/T3.
- Control Input (A1, A2): Konektatu kontrola voltage to terminals A1 and A2.
- Use recommended wire sizes (e.g., 0.75-6mm² or 18-10AWG for power, 0.5-1.5mm² or 20-16AWG for control) and tighten terminals to the specified torque (e.g., 0.5Nm or 4.4lb-in for M3 screws).
5.3 Hasierako ezarpenak
Before initial operation, adjust the potentiometers on the front panel (Figure 3.2) to desired settings:
- Ramp Gora denbora: Adjust the 'up' potentiometer to set the motor acceleration time (0-10 seconds).
- Ramp Down Time: Adjust the 'down' potentiometer to set the motor deceleration time (0-10 seconds).
- Hasiera eman: Adjust this potentiometer to provide an initial torque boost for starting loads.
- Initial Torque: Adjust this potentiometer to set the initial torque level during startup.
6. Funtzionamendu-argibideak
Once installed and configured, the Danfoss MCI 15 Motor Controller operates by applying a controlled voltageramp to the motor, providing a soft start and stop. The motor will accelerate to full speed over the set ramp-up time and decelerate over the set ramp-behera denbora.
- Aplikatu kontrola voltage to terminals A1 and A2 to initiate motor operation.
- Remove control voltage to initiate motor stop (soft stop).
- Monitor motor performance and adjust ramp times and torque settings as needed for optimal operation.
7. Mantentzea
Regular maintenance ensures the longevity and reliable operation of the motor controller.
- Garbiketa: Periodically clean the exterior of the controller, especially the heat sink fins, to ensure proper heat dissipation. Use a dry, soft cloth. Do not use solvents or abrasive cleaners.
- Ikuskapena: Regularly inspect wiring connections for tightness and signs of wear or damage. Check for any discoloration or unusual odors, which may indicate overheating.
- Ingurumena: Ziurtatu funtzionamendu-ingurunea tenperatura eta hezetasun-tarte jakin batzuen barruan mantentzen dela.
8. Arazoak
If the motor controller does not operate as expected, consider the following basic troubleshooting steps:
- No Motor Start: Verify power supply to the controller and motor. Check control signal to A1/A2. Ensure all wiring is correct and secure.
- Motor gainberotzea: Check for proper ventilation around the heat sink. Ensure the motor is not overloaded. Verify motor parameters are correctly set.
- Incorrect Ramp Orduak: Re-adjust the 'up' and 'down' potentiometers on the front panel.
- Unexpected Stops: Check for power fluctuations or intermittent control signals. Inspect for any fault indicators if available on the device or system.
For complex issues, contact Danfoss technical support.
9. Bermea eta Laguntza
For information regarding product warranty, technical support, or service, please refer to the official Danfoss website or contact your local Danfoss representative. Ensure you have the model number (MCI 15) and serial number (if applicable, visible on the rear label, Figure 7.1) available when contacting support.