ICM-UA2L-24C-DUAL Universal Refrigerant Leak Detection and Mitigation System Manual

Model: ICM-UA2L-24C-DUAL | Brand: ICM Controls

1. Sarrera

The ICM-UA2L-24C-DUAL A2L Refrigerant Leak Detection & Mitigation Control is a safety solution designed to support HVAC systems utilizing low-GWP A2L refrigerants. This system provides reliable refrigerant leak detection and coordinates mitigation responses for equipment using R-32 and R-454B refrigerants. It continuously monitors refrigerant concentration levels with compatible A2L refrigerant sensors. Upon leak detection, the control board activates alarm and mitigation signals to reduce risk and support safe system operation.

2. Segurtasun informazioa

Segurtasun-ohar garrantzitsua: Installation and servicing of this product must be performed by a qualified, professional HVAC technician. Improper installation or maintenance can lead to system malfunction, property damage, or personal injury. Always disconnect power before installing or servicing the unit.

Icon indicating that installation requires a professional or qualified person

This icon signifies that installation requires a professional or qualified person to ensure safety and proper function.

UL Listed logo with E365756

The UL Listed mark indicates that this product has been tested by UL and meets nationally recognized safety standards.

3. Produktua amaitu daview

The ICM-UA2L-24C-DUAL is powered by 24VAC and features dual sensor capability, allowing integration with multiple detection points within a single system. Built-in MODBUS communication enables efficient data exchange with sensors and HVAC control systems, supporting advanced diagnostics, monitoring, and automation.

Ezaugarri nagusiak

ICM-UA2L-24C-DUAL control board with a connected refrigerant sensor

The image shows the ICM-UA2L-24C-DUAL control board installed, with a connected refrigerant sensor being held by a gloved hand. This illustrates the system's primary components.

4. Instalazioa

4.1 Muntaketa

The control board is designed for secure mounting within an HVAC system enclosure. Utilize the four 1/2-inch standoffs provided. These standoffs are designed to lock into a 0.187-inch ±0.003 hole for stable installation.

Technical drawing showing the control board with mounting standoffs

This technical drawing illustrates the control board's mounting points, specifically highlighting the four 1/2-inch standoffs and the required hole size for secure installation.

4.2 Kableatua

Connect the 24VAC power supply to the designated terminals. The unit supports dual sensors, which should be connected to the 'SENSOR 1' and 'SENSOR 2' terminals. Alarm, fan, and control outputs are available via 1/4-inch quick connect terminals for integration with external mitigation devices such as ventilation fans or compressor shutdown circuits. Refer to the wiring diagram for specific connections.

Technical drawing showing the dimensions and wiring terminals of the control board

This technical drawing provides detailed dimensions of the control board and labels for all wiring terminals, including common (COM), alarm (ALM), fan (FAN), normally open (NO), normally closed (NC), and sensor inputs (SENSOR 1, SENSOR 2).

5. Funtzionamendua

5.1 Power-Up and Self-Test

Upon initial power-up, the system will perform a self-diagnostic check. During this period, the power LED will illuminate, and other indicator LEDs may cycle. Once the self-test is complete, the system will enter normal operating mode, indicated by a steady power LED.

5.2 Leak Detection and Mitigation Sequence

When a connected A2L refrigerant sensor detects refrigerant concentration exceeding a predefined threshold, the control board initiates a mitigation sequence:

5.3 LED adierazleak

The control board features visual LED indicators to provide system status at a glance:

6. Mantentzea

Regular maintenance ensures the continued reliability and accuracy of the leak detection system. It is recommended to:

7. Arazoak

This section provides solutions to common issues encountered with the ICM-UA2L-24C-DUAL system.

ArazoaKausa posibleaIrtenbidea
Sistema ez da piztenNo 24VAC power supply; loose wiring connectionVerify 24VAC power is supplied to the unit; check all power connections.
Alarm LED is active without a known leakSensor malfunction; false alarm; high background refrigerant levelInspect sensor for damage; verify sensor calibration; ventilate area and re-evaluate.
Fault LED is activeSensor disconnected or faulty; internal system errorCheck sensor connections; replace faulty sensor; if issue persists, contact technical support.
Mitigation actions (fan/compressor shutdown) not activatingWiring error to external devices; external device malfunctionVerify wiring to fan/compressor control circuits; test external devices independently.

8. Zehaztapenak

ZehaztapenaBalioa
EreduaICM-UA2L-24C-DUAL
Potentzia Sarrera24 VAC
Hozgarrien bateragarritasunaR-32, R-454B (A2L refrigerants)
Sensor CapabilityDual sensor support
KomunikazioaMODBUS
IrteerakDry contact alarm, fan, control outputs
Paketearen neurriak8 x 6 x 2.5 hazbete
Elementuaren pisua1.2 kilo
FabrikatzaileaICM kontrolak

9. Bermearen informazioa

ICM Controls products are manufactured to high standards and are backed by a manufacturer's warranty. For specific warranty terms and conditions, please refer to the documentation included with your product or visit the official ICM Controls webgunea. Gorde erosketaren egiaztagiria bermearen erreklamazioetarako.

Seal stating 'Best Warranty In The Industry Made In America'

This seal highlights the manufacturer's commitment to quality and warranty support for products made in America.

10. Laguntza Teknikoa

If you encounter issues not covered in this manual or require further assistance, please contact ICM Controls technical support. Have your product model number and any relevant diagnostic information ready when you call or email.

For the most up-to-date contact information, please visit the official ICM Controls webgunea: www.icmcontrols.com

Erlazionatutako dokumentuak - ICM-UA2L-24C-DUAL

Aurreview ICM-UA2L-24C-DUAL R32 & R454B A2L Refrigerant Detection System - Installation, Operation & Application Guide
Comprehensive guide for the ICM-UA2L-24C-DUAL A2L Refrigerant Detection System, detailing installation, operation, specifications, features, and troubleshooting for R32 and R454B refrigerants. Includes wiring diagrams and mounting instructions.
Aurreview ICM-UA2L-24C-DUAL R32 & R454B A2L Refrigerant Detection System Installation, Operation & Application Guide
Comprehensive guide for the ICM-UA2L-24C-DUAL system, detailing installation, operation, specifications, features, and troubleshooting for R32 and R454B A2L refrigerants. Includes wiring diagrams and status indicators.
Aurreview ICM325A Fase Bakarreko Presio Kontrol Unibertsalaren Instalazio Gida
ICM325A Fase Bakarreko Presio Kontrol Unibertsalaren instalazio, funtzionamendu eta aplikazio gida. ICM Omni aplikazioaren bidez programatzeko NFC teknologia, sentsore bikoitzeko sarrerak, bero-ponparen bypass-a eta bolumen unibertsala ditu.tage.
Aurreview ICM-UFPT-2 eta ICM-UFPT-5 Funtzio Unibertsaleko Tenporizadore Programagarrien Instalazio eta Erabilera Gida
ICM Controls ICM-UFPT-2 eta ICM-UFPT-5 funtzio unibertsaleko programazio-tenporizadoreen instalazio, funtzionamendu eta aplikazio gida osoa, NFC teknologiarekin konfigurazio eta programazio errazerako.
Aurreview ICM i3 Wi-Fi Programmable Thermostat: Installation, Operation, and Application Guide
This guide provides comprehensive instructions for installing, operating, and configuring the ICM i3 Wi-Fi Programmable Thermostat. It covers features, specifications, wiring diagrams, troubleshooting, and Wi-Fi setup for HVAC systems.
Aurreview ICM-UDEFROST Desizozte Kontrol Unibertsala Instalatzeko, Erabiltzeko eta Aplikaziorako Gida
ICM-UDEFROST Desizozte Kontrol Unibertsalaren gida osoa, HVAC sistemetarako instalazioa, funtzionamendua, ezaugarriak, zehaztapenak, kableatu diagramak, proba moduak, diagnostikoak eta NFC konfigurazioa zehaztuz.